Solar Structure Wind Load Calculation as per IS 875 Part 3: Method, Factors and Example
Solar Structure Wind Load Calculation as per IS 875 Part 3
Wind is the load most often governing the design of a solar mounting structure. Modules are light, they present a large tilted surface, and the net force on that surface can act upward as well as downward. Getting the wind calculation wrong is the quickest way to get the whole structural design wrong.
This article explains the calculation chain in IS 875 (Part 3):2015, what each variable means, how the result becomes a load on purlins, rafters, columns and foundations, and where the code does not give you the answer. It supports our pillar guide on solar structure design using STAAD.Pro.
Verification note: The formulas below follow the structure of IS 875 (Part 3):2015 as reflected in Bentley's documentation, Solyug Energy's published methodology and secondary technical summaries. Table values, clause numbers and coefficients must be read from the official BIS copy, including its amendments, for the edition your project adopts. Values used in the worked example are assumed for illustration and are not code values.
Why wind load is critical in solar structure design
A tilted array behaves aerodynamically like a series of low canopy surfaces. Wind can press the modules down against the frame or suck them upward and away from it. Because the structure is light, uplift can be large compared with dead load, so anchors, base plates, connections and foundations are checked for tension as well as compression. Wind also creates horizontal force and an overturning moment on the whole table.
The calculation chain
IS 875 (Part 3):2015 turns a regional wind speed into a design pressure in stages:
Step | Quantity | Expression |
1 | Basic wind speed | Vb from the wind map or city table |
2 | Design wind speed | Vz = Vb × k1 × k2 × k3 × k4 |
3 | Design wind pressure | pz = 0.6 × Vz² |
4 | Pressure after reduction factors | pd = Kd × Ka × Kc × pz |
5 | Net pressure on the surface | p = (Cpe − Cpi) × pd, or the net coefficient from the relevant table |
6 | Force | F = p × A |
Variables and units
Symbol | Meaning | Unit |
Vb | Basic wind speed: 3-second gust at 10 m height, open terrain, 50-year return period | m/s |
k1 | Probability (risk) factor, depends on design life and region | none |
k2 | Terrain, height and structure-size factor | none |
k3 | Topography factor | none |
k4 | Importance factor for cyclonic regions | none |
Vz | Design wind speed at height z | m/s |
pz | Design wind pressure at height z (0.6 is a constant for SI units, with Vz in m/s giving pz in N/m²) | N/m² |
Kd | Wind directionality factor | none |
Ka | Area averaging factor | none |
Kc | Combination factor | none |
pd | Design wind pressure after reduction factors | N/m² |
Cpe, Cpi | External and internal pressure coefficients | none |
A | Surface area | m² |
F | Wind force | N |
Basic wind speed
IS 875 (Part 3):2015 groups India into wind zones with basic wind speeds of 33, 39, 44, 47, 50 and 55 m/s, which Solyug Energy's STAAD Pro wind analysis page also describes. The value for a site comes from the code's wind map or its table of cities. Sites near coasts can fall in the highest zones. When a site lies between listed locations, take the value for the zone of the site and record the source.
Risk coefficient (k1)
k1 adjusts the wind speed for the probability of exceedance over the design life and for whether the site is in a cyclonic region. Solar plants are often designed for a 25-year life, but many owners and lenders specify a 50-year basis. The correct choice is a design-basis decision that should be agreed with the client and written down. Read k1 from the code's table for the chosen life and region.
Terrain category and height (k2)
The code groups terrain into four categories according to surface roughness, from open terrain with few obstructions to dense built-up areas with tall obstructions. k2 depends on the category, the height above ground and the size of the structure. Solar tables are low, so height is usually small, but the terrain category should be justified by what actually surrounds the array now and for the plant's life. Plant boundaries, buildings and tree lines can change the category.
Topography factor (k3)
k3 raises the design speed where the wind accelerates over hills, ridges and escarpments, and is 1.0 for flat sites. Ground-mounted plants on hill slopes or rooftops near cliff-like edges need the code's topography procedure and not a default value of 1.0.
Cyclonic importance factor (k4)
The 2015 edition introduced k4 for structures in cyclone-prone regions, with values that depend on the class of structure. Check whether the project is in a cyclonic region and select k4 from the code accordingly.
Design wind pressure
From Vz, the pressure is pz = 0.6 Vz². The factors Kd, Ka and Kc then reduce the pressure in certain cases:
• Kd accounts for the low probability that the strongest wind hits from the worst direction.
• Ka reduces the pressure on large tributary areas, because gusts are not fully correlated across a big surface.
• Kc applies when the effects of pressures on several surfaces are combined.
These reductions apply only under the code's stated conditions. Using them without checking applicability is a common source of under-design.
Pressure coefficients: where solar differs from buildings
IS 875 (Part 3) gives pressure coefficients for buildings, roofs, canopies and other structures. It does not give coefficients developed specifically for tilted solar module arrays. SgurrEnergy's technical paper makes the same point about current design standards generally and argues for applying the monoslope canopy provisions with eccentric loading rather than a uniform pressure.
Engineers therefore usually apply the code provisions for open (free-standing) monoslope roofs to a solar table, as the nearest available analogue. Points to handle carefully:
• Do not assume building wall or roof coefficients apply directly. Enclosed-building external and internal coefficients (Cpe − Cpi) describe a different flow situation from an open table with air flowing above and below.
• Use the net coefficients for open roofs where the code gives them, read for the correct tilt angle and wind direction, and note that they differ between the windward and leeward portions.
• Check the effect of eccentric loading. Where the resultant of pressure sits away from the table centre, rafters, columns and foundations see different forces than under uniform pressure.
• Consider edge and corner zones where peak local pressures are higher, which affects purlin and fastener checks.
• Consider row interaction. Rear rows of an array are partly sheltered. Bentley notes that codes usually allow shielding to be considered in optimised designs, but that judgement is required. We have not found explicit solar-row shielding factors in IS 875 (Part 3) that can be quoted without project-specific justification.
When specialist data or a wind tunnel study may be required
Consider specialist guidance, boundary-layer wind tunnel testing or computational fluid dynamics when:
• the array is large, tall, unusually tilted or has an unusual geometry (very low clearance, closely packed rows, tracker systems)
• the site has complex terrain or a nearby large structure
• the design is novel or the client or lender requires site-specific aerodynamic data
• code coefficients are clearly not representative
Tracker systems also involve dynamic effects such as torsional galloping, which are outside simple static design.
Uplift, lateral force and overturning
The net pressure acts normal to the module plane. Resolve it into a vertical component (uplift or downward) and a horizontal component:
• Vertical component = F cos θ
• Horizontal component = F sin θ
where θ is the tilt angle. The vertical uplift is resisted by the dead load and by foundation pull-out capacity. The horizontal component produces sliding and, together with the vertical component acting at an eccentricity, an overturning moment about the base.
Worked illustration with assumed values
The following illustration uses invented inputs to show the arithmetic. It is not a design for any real site.
Assumed inputs: Vb = 44 m/s; k1 = 1.0; k2 = 1.0 (a deliberately simple assumption for a low structure); k3 = 1.0; k4 = 1.0; Kd = 0.9; Ka = 1.0; Kc = 1.0. Table: 2 modules high in portrait × 12 modules wide, each module 2.2 m × 1.1 m, giving a sloping length of 4.4 m, a width of 13.2 m and an area of 58.08 m². Tilt 15°. Net pressure coefficients are assumed as +0.8 (downward) and −1.0 (uplift) for illustration only.
Quantity | Calculation | Result |
Design wind speed Vz | 44 × 1.0 × 1.0 × 1.0 × 1.0 | 44 m/s |
Pressure pz | 0.6 × 44² | 1,161.6 N/m² |
Reduced pressure pd | 0.9 × 1,161.6 | 1,045.4 N/m² |
Uplift pressure (assumed C = −1.0) | 1,045.4 × 1.0 | 1.045 kN/m² |
Downward pressure (assumed C = +0.8) | 1,045.4 × 0.8 | 0.836 kN/m² |
Normal uplift force on table | 1.045 × 58.08 | 60.7 kN |
Vertical component | 60.7 × cos 15° | 58.7 kN |
Horizontal component | 60.7 × sin 15° | 15.7 kN |
The same assumed case is carried forward in our articles on dead, imposed and wind loads and solar structure design calculations.
Load transfer to the structure
Pressure on modules becomes a line load on each purlin according to its tributary width. Purlins deliver reactions to rafters at their connections. Rafters deliver forces to columns, and columns to the foundation, including uplift tension, horizontal shear and moment. Each member, connection and foundation must be checked for the combination that governs it, which is covered in load cases and load combinations for solar mounting structures.
Wind load in STAAD.Pro
STAAD.Pro includes an IS 875 (Part 3):2015 wind load generator, but its documentation lists rectangular clad buildings and unclad frame buildings as the supported structure types. For a solar table the usual approach is to calculate the pressure as above and apply it to the model manually. The procedure is explained in how to apply wind loads in STAAD.Pro for solar structures.
Common mistakes
• Using enclosed-building coefficients for an open table
• Applying reduction factors Kd, Ka or Kc without checking conditions
• Using one wind direction and one load sign
• Using Vb from the wrong zone or without recording the source
• Ignoring topography and local terrain changes
• Forgetting that wind uplift reverses the sign of column and foundation forces
Frequently asked questions
How is wind load calculated for solar panels?
Determine the basic wind speed for the site, convert it to design wind speed with the k-factors, calculate design pressure, apply the appropriate net pressure coefficients for the array geometry and multiply by the exposed area. Then resolve and apply the load to the structural model.
What is the formula for design wind speed in IS 875 Part 3?
Vz = Vb × k1 × k2 × k3 × k4, and the design pressure is pz = 0.6 Vz² in N/m² with Vz in m/s. Read each factor from the code's tables for the project.
Why is uplift critical for solar structures?
The structure is light and the module surface large, so suction can exceed the downward weight. That makes anchors, connections, columns and foundations tension-critical.
Can building pressure coefficients be used for solar panels?
Not automatically. IS 875 (Part 3) does not provide coefficients developed for tilted solar arrays. Engineers use the nearest applicable provisions, typically for open roofs, with judgement and, where needed, specialist data.
When is a wind tunnel test needed?
When the array geometry, site or project requirements go beyond what code coefficients represent, for example large or unusual arrays, complex terrain, or when a lender requires site-specific data.
Does STAAD.Pro calculate wind loads on solar tables automatically?
Its IS 875 (Part 3):2015 generator targets buildings and unclad frames. Solar-array wind loads are normally calculated separately and applied by the engineer.
Conclusion
A reliable solar wind calculation traces every number from the basic wind speed to the force on each member, states which code provisions are used and flags where judgement replaces code coverage. That traceability is what reviewers, lenders and certifying authorities look for.
Get a traceable wind load calculation for your solar project
Solyug Energy prepares STAAD Pro wind analysis for solar structures with the calculation chain from basic wind speed to member and foundation checks, as described on the service page. For wider design support see our solar structural consultancy or contact the team with your site location and layout.